Most questions about air do not concern absolute pressure, but rather a difference. How much resistance has the filter built up? What is the pressure drop across the heat exchanger? Is the operating room at a higher or lower pressure than the corridor? None of these questions can be answered by a single pressure reading — they are answered by the difference between two points.
This is why the instrument has two connections. With one connection, you measure against the atmosphere, which fluctuates with the weather and the floor level. With two, you measure between two points within the same system, meaning it no longer matters if the outdoor air pressure has risen since this morning.
What it is
Comark C9551 — a pressure gauge for dry gases, designed for low pressures.
- Measurement range 0 to ±140 mbar, equivalent to 0-2 PSI, 0-1400 mmH2O or 0-9999 Pa
- Dual inputs with 1/8-inch BSP connections — for gauge pressure or differential pressure
- IP67, dust- and watertight housing according to BS EN 60529
- Max and min values, warnings for over- and under-pressure, and low battery
- Up to 125 hours of operation on a 9V battery, with automatic shut-off
- Supplied with 1.4 m polyurethane hose, nylon washers, and connectors
What the units reveal
The fact that the display offers mmH2O and inH2O says something about the scale. At these pressures, a water column has historically been used as the measuring standard, essentially a U-shaped glass tube filled with water. The full scale of this instrument — 140 mbar — corresponds to a water column of 1.4 meters. This provides a useful sense of scale: a clogged ventilation filter typically involves a pressure drop on the order of a few hundred pascals, which is equivalent to a few centimeters of water column.
This is precisely why a resolution down to single pascals matters. The difference between a clean and a loaded filter is small in absolute terms but critical for airflow — if you measure with an instrument designed for bars, this difference will not be visible at all.
Why “dry gases” is a real limitation
It is in the product name for a reason. Moisture in the measuring hose does not only damage the sensor in the long term — it destroys the measurement immediately. Condensation that collects in a hose forms its own liquid column, and that column adds its own pressure to what you are trying to measure. Since the condensation also moves when the hose changes slope, the error becomes both large and unstable.
Practically, this means: route the hoses so that any moisture runs away from the instrument, not towards it, and do not measure directly in a flow that carries liquid. It is a simple habit, but it is the difference between an instrument that remains reliable for years and one that becomes unreliable after the first season.
Three typical use cases
- Ventilation: pressure drop across filters and heat exchangers, as well as duct pressure during commissioning.
- Pressure hierarchy in rooms: verifying that clean rooms, kitchens, or isolation rooms are at the correct pressure relative to adjacent areas.
- Gas and combustion technology: checking connection pressure and draft conditions, where values are far below one bar.
Why it is worth it
Filters are almost always replaced based on a calendar, not on their condition. This results in two types of losses simultaneously: filters that are discarded while still functioning, and filters that are kept too long and restrict airflow — which costs fan energy every hour and degrades indoor climate in the meantime.
Pressure drop is the only measurement that actually describes the filter’s condition, and it takes one minute. For a facility with many units, it is often the single simplest measure that both reduces electricity consumption and extends the time between filter changes — at the same time.